Products
Home > Products
Residual Current Circuit Breakers — LGL Series RCCB
Back
Detailed description

Applicable scope:

LGL series residual current circuit breakers are applied to the lines with AC 50/60Hz,rated voltage of 230V(1P+N) or 400V(3P+N),and rated current of 100A.In case of electric shock or electric leakage current exceeds the specified value,the residual current circuit breaker can switch off the fault circuit in a very short time,protecting the safety of person and electric equipment.
Can be used in the industrial,commercial,high-rise buildings,civil residences and other places.

Number of poles

1P+N,3P+N
Rated current(In)
A
25,32,40,63,80,100
Rated operating voltage(Ue)
V
230V(1P+N),400V(3P+N)
Rated frequency
Hz
50/60
Rated insulation voltage(Ui)
V
500
Rated residual current (IΔn)
mA
10, 30, 100, 300
Rated residual switching on and breaking capacity(IΔm)
A
500(In=25A/32A/40A), 630(In=63A) ,800(In=80A),1000(In=100A)
Rated residual short-circuit current limit(IΔc)
A
6000  10000
Rated short-circuit current limit(Inc)
A
6000  10000
Rated switching on and breaking capaity(Im)
A
500(In=25A/32A/40A),630(In=63A) ,800(In=80A),1000(In=100A)
SCPD fuse
A
Matched silver wire
Maximun breaking time(IΔm)
S
0.3
Rated impulse withstand voltage(Uimp)
kV
6
Dielectric strength of main circuit
(1 min power frequency withstand voltage test)
kV
2.5
Pollution degree 

2
Electrical and mechanical life
times
4000
Residual current action indication

Standard operation condition Protection degree

IP20
Standard operation condition  Ambient temperature
-5℃~+40℃ and its average over aperiod of 24h does not exceed +35℃
Standard operation condition Storage temperature
-25℃to+55℃,for short periods not exceeding 24h,up to +70℃
Standard operation condition Altitude
m
≤2000
Terminal connection types

type cable,type U bus,type bus
Wiring terminal connection conductor
mm²
1.5~25
Wiring terminal copper size
mm²
25
Tightening torque
N*m
3.5
Installation mode

UsingTH3.5-7.5 profile installation, the title of installation face and vertical face is not greater than5°
Wiring incoming mode

upper and lower incoming is possible


Copyright © 2018 Anhonor Electric Co., Ltd All Rights Reserved 版权所有 浙ICP备18033980号-1